YAS_FP605_HVAC
Yaskawa FP605 MEMOBUS/Modbus driver — HVAC fan duty with process PI and a fire/smoke override that outranks the restart lockout.
When to use it
Use YAS_FP605_HVAC when a Yaskawa FP605 drives a building fan or pump over MEMOBUS/Modbus, the PLC closes the process loop, and a fire-alarm input must drive the machine to a commanded speed regardless of the normal control.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| RUN | BOOL | — |
| FIRE | BOOL | — |
| FIRE_SPD | REAL | % |
| PID_EN | BOOL | — |
| SP | REAL | process units |
| PV | REAL | process units |
| SPD_CMD_PCT | REAL | % |
| SPD_MIN | REAL | % |
| SPD_MAX | REAL | % |
| KP | REAL | % per process unit |
| TI_S | REAL | s |
| REV_ACTING | BOOL | — |
| STATUS_WORD | WORD | — |
| FREQ_OUT_WORD | WORD | — |
| COMMS_OK | BOOL | — |
| COMMS_TMO | TIME | — |
| O1_03 | INT | — |
| MAX_FREQ_HZ | REAL | Hz |
| MON_HZ_PER_COUNT | REAL | Hz/count |
| NET_SELECT | BOOL | — |
| REQ_NET_CTRL | BOOL | — |
| MFI_MASK | WORD | — |
| EXT_TRIP | BOOL | — |
| FAULT_RST | BOOL | — |
| RST_QUIESCE_T | TIME | — |
| RST_PULSE_T | TIME | — |
| RST_VERIFY_T | TIME | — |
Outputs
| Port | Type | Unit |
|---|---|---|
| SPEED_PCT | REAL | % |
| FIRE_MODE | BOOL | — |
| CTRL_WORD | WORD | — |
| FREQ_REF_WORD | WORD | — |
| REF_HZ | REAL | Hz |
| READY | BOOL | — |
| RUNNING | BOOL | — |
| REVERSING | BOOL | — |
| FAULT | BOOL | — |
| RESETTING | BOOL | — |
| SPD_ACT | REAL | Hz |
| MFDO1 | BOOL | — |
| NET_REF_OK | BOOL | — |
| NET_CTRL_OK | BOOL | — |
| TELEGRAM_STALE | BOOL | — |
| ALM_COMMS | BOOL | — |
| ALM_RESET_FAILED | BOOL | — |
| ALM_NOT_IN_NET | BOOL | — |
| ALM_DATA_SETTING | BOOL | — |
| ALM_SCALE_UNKNOWN | BOOL | — |
| ALM_REF_CLAMP | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
| ALM_MON_UNSCALED | BOOL | — |
| ALM_DIR_MISMATCH | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
YAS_FP605_HVAC commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 23
- Simulated scans
- 462
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499
Download YAS_FP605_HVAC — free
Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.
Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.
Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.