WFI_LOOP_MON

WFI distribution-loop monitor — TOC, USP <645> temperature-stepped conductivity and hot-loop temperature, with a use permissive.

Validated application blockLS · Water SystemsIEC 61131-3v1.0.0

When to use it

Use WFI_LOOP_MON when a water-for-injection distribution loop carries on-line TOC and conductivity analysers and a return-temperature element, and the control system has to hold a continuous use permissive for the points of use on the loop.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
PARAMSSTRING—
TOC_PVREALppb
TOC_OKBOOL—
COND_PVREALuS/cm
COND_OKBOOL—
TEMP_PVREALdegC
TEMP_OKBOOL—
TOC_LIMREALppb
COND_LIMREALuS/cm
TEMP_MINREALdegC
CONFIRMTIME—
RETURN_DLYTIME—
ACKBOOL—

Outputs

PortTypeUnit
TOCREALppb
CONDREALuS/cm
TEMPREALdegC
OKBOOL—
COND_LIM_APPLREALuS/cm
VALIDBOOL—
ALM_TOC_HIGHBOOL—
ALM_COND_HIGHBOOL—
ALM_TEMP_LOWBOOL—
ALM_SENSOR_FAULTBOOL—
ALM_TEMP_RANGEBOOL—

Validation evidence

Tests
9
Simulated scans
226
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download WFI_LOOP_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.