VAV_BOX_CTRL

Pressure-independent VAV terminal box with dual-maximum reheat and a starved-flow alarm.

Validated application blockBAS · Air HandlingIEC 61131-3IEC 61499v1.0.0

When to use it

Use VAV_BOX_CTRL when a VAV terminal unit serves one zone from a variable-pressure trunk, with a measured airflow (a flow cross or velocity sensor) and optionally a reheat coil.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
OCCBOOL
ZONE_TEMPREAL°C
ZONE_SPREAL°C
ZONE_OKBOOL
FLOWREALl/s
FLOW_OKBOOL
FLOW_MINREALl/s
FLOW_MAXREALl/s
FLOW_HTG_MAXREALl/s
FLOW_MIN_UNOCCREALl/s
DB_KREALK
KP_ZREAL%/K
TI_ZTIME
KP_FREAL%/(l/s)
TI_FTIME
FLOW_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
DMPR_POSREAL%
REHEAT_VLVREAL%
FLOW_SPREALl/s
COOLINGBOOL
HEATINGBOOL
VALIDBOOL
ALM_ZONE_FAULTBOOL
ALM_FLOW_FAULTBOOL
ALM_FLOW_LOWBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
120
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download VAV_BOX_CTRL — free