UPS_BYPASS_CTRL

Supervised UPS static-bypass transfer with an ANSI 25 synchro-check, a two-person rule and position proof.

Validated application blockDCIM · Power ChainIEC 61131-3IEC 61499v1.0.0

When to use it

Use UPS_BYPASS_CTRL when a static UPS must be transferred to and from its static bypass under supervision — for maintenance, for a load bank, or because the inverter has failed — and the transfer has to be blocked when the inverter and the bypass source are not synchronised.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
REQ_BYPASSBOOL
REQ_INVERTERBOOL
AUTH_ABOOL
AUTH_BBOOL
SYNC_OKBOOL
LOAD_PCTREAL%
DV_PCTREAL%
DF_HZREALHz
DPHI_DEGREALdeg
V_INV_PCTREAL%
V_BYP_PCTREAL%
DV_MAX_PCTREAL%
DF_MAX_HZREALHz
DPHI_MAX_DEGREALdeg
V_LIVE_PCTREAL%
XFER_MAX_LOAD_PCTREAL%
INV_FAULTBOOL
BYP_FBBOOL
XFER_TMOTIME
ACKBOOL

Outputs

PortType
ON_BYPASSBOOL
ON_INVERTERBOOL
PERMITBOOL
AUTH_OKBOOL
XFER_BLOCKEDBOOL
ALM_SYNC_FAILBOOL
ALM_XFER_FAILBOOL
ALM_UNSYNC_XFERBOOL
ALM_NO_PATHBOOL
ALM_AUTHBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
12
Simulated scans
155
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download UPS_BYPASS_CTRL — free