SUPPLY_TEMP_AVG

Six-channel supply-air aggregation with per-channel range rejection, minimum/average/maximum, stratification spread and ASHRAE envelope alarms.

Validated application blockDCIM · CoolingIEC 61131-3v1.0.0

When to use it

Use SUPPLY_TEMP_AVG when several supply-air or rack-inlet sensors cover one zone and the supervisory loop needs a single trustworthy minimum, average and maximum from them without a dead channel corrupting the result.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
T1REALdegC
T2REALdegC
T3REALdegC
T4REALdegC
T5REALdegC
T6REALdegC
OK1BOOL—
OK2BOOL—
OK3BOOL—
OK4BOOL—
OK5BOOL—
OK6BOOL—
N_SENSORSUSINT—
MIN_SENSORSUSINT—
RANGE_LOREALdegC
RANGE_HIREALdegC
HI_LIMITREALdegC
HI_HI_LIMITREALdegC
CONFIRMTIME—
ACKBOOL—

Outputs

PortTypeUnit
T_MINREALdegC
T_AVGREALdegC
T_MAXREALdegC
SPREADREALK
N_GOODUSINT—
VALIDBOOL—
ALM_SENSOR_LOSSBOOL—
ALM_HIGHBOOL—
ALM_HIGH_HIGHBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
7
Simulated scans
77
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download SUPPLY_TEMP_AVG — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.