STDDEV_WIN

Windowed standard deviation by the two-pass method, with the window mean published alongside.

Validated application blockEdge AnalyticsIEC 61131-3IEC 61499v1.0.0

When to use it

Use STDDEV_WIN when the variability of a signal is the diagnostic — a control loop that is hunting, a chiller short-cycling, a flow meter starting to cavitate, a charger current that has become ragged — and a number is wanted for the noise itself rather than for the level.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
INREALEU
IN_OKBOOL
WINDOWUINT
SAMPLE_SDBOOL
SAMPLE_TTIME
RESETBOOL
ACKBOOL

Outputs

PortTypeUnit
OUTREALEU
MEANREALEU
VALIDBOOL
N_VALIDUINT
ALM_SIG_FAULTBOOL
ALM_CFG_ERRBOOL
ALM_UNDERSAMPLEDBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
65
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download STDDEV_WIN — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.