STAIR_PRESS_CTRL

Stairwell pressurisation with anti-windup PI fan control, over-pressure relief modulation and latched code-window trouble.

Validated application blockBAS · Lighting, IAQ & EnergyIEC 61131-3IEC 61499v1.0.0

When to use it

Use STAIR_PRESS_CTRL when a stair shaft is pressurised on a fire-alarm command through a variable-speed fan and a modulating relief damper, and the differential pressure has to be held inside a code window while doors open and close.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ACTIVATEBOOL
DPREALPa
DP_OKBOOL
DP_SPREALPa
DOOR_OPENBOOL
DP_MINREALPa
DP_MAXREALPa
KPREAL%/Pa
TIREALs
MIN_SPEED_PCTREAL%
DOOR_SPEED_PCTREAL%
FAILSAFE_PCTREAL%
FAILSAFE_RELIEF_PCTREAL%
TROUBLE_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
FAN_SPEEDREAL%
RELIEF_DMPRREAL%
ACTIVEBOOL
DP_IN_BANDBOOL
CTRL_VALIDBOOL
ALM_DP_LOWBOOL
ALM_DP_HIGHBOOL
ALM_DP_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
341
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499