SOFT_LOAD_RAMP

Soft loading after breaker close — a rate-limited kW ramp from the machine's present output to its target share.

Validated application blockGen · Load SharingIEC 61131-3IEC 61499v1.0.0

When to use it

Use SOFT_LOAD_RAMP when a set has just been synchronised and paralleled and must pick up its share of load smoothly, rather than being handed a step change the moment its breaker closes.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
STARTBOOL
BRK_CLOSEDBOOL
KWREALkW
KW_OKBOOL
KW_RATEDREALkW
RATE_KW_SREALkW/s
TARGET_PCTREAL%
DONE_BAND_PCTREAL%
CONFIRM_TTIME
RAMP_TMOTIME
KPREAL%/%
TIREALs
BIAS_LIMREAL%
ACKBOOL

Outputs

PortTypeUnit
BIASREAL%
KW_SPREALkW
PCT_LOADREAL%
RAMPINGBOOL
DONEBOOL
AT_TARGETBOOL
AT_LIMITBOOL
VALIDBOOL
ALM_RAMP_TMOBOOL
ALM_KW_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
11
Simulated scans
277
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download SOFT_LOAD_RAMP — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.