SIP_50BF_CBF

SIPROTEC-shaped breaker-failure protection (ANSI 50BF): a current-based failure criterion with an optional 52a contact criterion, a two-stage timer giving re-trip then bus strip, and a sealed-in bus trip.

Validated application blockPSUB·SiemensIEC 61131-3IEC 61499v1.0.0

When to use it

Use SIP_50BF_CBF when a breaker's trip has to be proved, and the surrounding breakers tripped if it is not — a busbar-connected feeder, a transformer or generator breaker, any circuit where a failed breaker leaves a fault fed from the bus.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
IaREALx In
IbREALx In
IcREALx In
cb52aBOOL
tBFTIME
STARTBOOL
ENABLEBOOL
CT_OKBOOL
IsetREALx In
tRetripTIME
USE_52ABOOL
ACKBOOL

Outputs

PortTypeUnit
busTripBOOL
reTripBOOL
ImaxREALx In
CURRENT_FLOWBOOL
BF_TIMINGBOOL
BLOCKEDBOOL
ALM_CT_FAILBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
12
Simulated scans
440
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download SIP_50BF_CBF — free