SE_ATV930_VFD
Schneider Altivar Process 900 (ATV930) CiA 402 drive telegram — control-word state machine, status decode, 0.1 Hz reference scaling and fault-acknowledge sequencing.
When to use it
Use SE_ATV930_VFD when an Altivar Process 900 drive is commanded over a fieldbus and the controller has to assemble the CiA 402 control word, decode the status word, and sequence starting, stopping and fault acknowledge itself.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| ENABLE | BOOL | — |
| RUN | BOOL | — |
| STATUS_WORD | WORD | — |
| ACT_SPD_W | INT | — |
| COMMS_OK | BOOL | — |
| COMM_TMO | TIME | — |
| FAULT_RST | BOOL | — |
| HALT | BOOL | — |
| FAILSAFE_QSTOP | BOOL | — |
| SEQ_TMO | TIME | — |
| RST_HOLD_T | TIME | — |
| SPD_REF | REAL | Hz |
| DIR | BOOL | — |
| REF_MAX_HZ | REAL | Hz |
Outputs
| Port | Type | Unit |
|---|---|---|
| CTRL_WORD | WORD | — |
| REF_WORD | INT | — |
| SPD_CMD_HZ | REAL | Hz |
| SPD_ACT | REAL | rpm |
| DRIVE_STATE | INT | — |
| READY | BOOL | — |
| OP_ENABLED | BOOL | — |
| AT_SPEED | BOOL | — |
| HALT_ACT | BOOL | — |
| FAULT | BOOL | — |
| WARNING | BOOL | — |
| QUICK_STOP_ACT | BOOL | — |
| LIMIT_ACT | BOOL | — |
| POWER_STAGE_OK | BOOL | — |
| REMOTE | BOOL | — |
| REVERSE_ACT | BOOL | — |
| STOP_KEY | BOOL | — |
| ALM_COMMS | BOOL | — |
| ALM_SEQ_TMO | BOOL | — |
| ALM_NOT_REMOTE | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
SE_ATV930_VFD commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 17
- Simulated scans
- 244
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499
Download SE_ATV930_VFD — free