SED_BASIN_MON

Sedimentation basin sludge-blanket monitor with a desludge call, rate-of-rise detection and a latched carry-over alarm.

Validated application blockW/WW · Treatment ProcessIEC 61131-3IEC 61499v1.0.0

When to use it

Use SED_BASIN_MON when a clarifier, plate settler or DAF basin carries an ultrasonic or optical sludge-blanket detector, and the desludge pump or scraper is to be called on blanket depth rather than on a fixed timer.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
BLANKET_MREALm
BLANKET_OKBOOL
BLANKET_MAXREALm
BLANKET_HI_MREALm
BLANKET_HYST_MREALm
RANGE_MAX_MREALm
HIGH_PERSIST_TTIME
RISE_WIN_TTIME
RISE_MAX_M_HREALm/h
ACKBOOL

Outputs

PortTypeUnit
OKBOOL
VALIDBOOL
DESLUDGE_REQBOOL
RISE_M_HREALm/h
FREEBOARD_MREALm
ALM_BLANKET_HIGHBOOL
ALM_RISING_FASTBOOL
ALM_SENSOR_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
179
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download SED_BASIN_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.