RECONNECT_SUPERVISOR

IEEE 1547 return-to-service supervision: withholds the reconnect permissive until voltage and frequency have held the window for the full stabilization period.

Validated application blockMG · PCC & ProtectionIEC 61131-3IEC 61499v1.0.0

When to use it

Use RECONNECT_SUPERVISOR when a DER or microgrid has ceased to energize and must not return until the area EPS has been demonstrably stable for the period in its interconnection agreement — typically five minutes.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
V_PUREALpu
FREQREALHz
MEAS_OKBOOL
BLOCK_INBOOL
V_LO_PUREALpu
V_HI_PUREALpu
F_LO_HZREALHz
F_HI_HZREALHz
STABLE_TTIME

Outputs

PortType
PERMITBOOL
BLOCKBOOL
T_REMAINTIME
IN_WINDOWBOOL
RESTARTSUDINT
ALM_MEAS_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
170
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download RECONNECT_SUPERVISOR — free