RACK_KW_MON
Dual-feed rack power monitor with per-feed continuous-load limits, A/B redundancy loss detection, dead-feed latching and energy totalising.
When to use it
Use RACK_KW_MON when a rack is fed from two independent A and B supplies through metered rack PDUs, and the site needs the rack's power and energy for capacity and PUE reporting AND needs to know before a single feed failure can trip the survivor.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| ENABLE | BOOL | — |
| KW_A_RAW | REAL | kW |
| KW_B_RAW | REAL | kW |
| A_OK | BOOL | — |
| B_OK | BOOL | — |
| DUAL_FEED | BOOL | — |
| FEED_A_PRESENT | BOOL | — |
| FEED_B_PRESENT | BOOL | — |
| FEED_KW_MAX | REAL | kW |
| LOAD_PCT_MAX | REAL | % |
| RACK_KW_MAX | REAL | kW |
| FEED_LOST_KW | REAL | kW |
| DB_PCT | REAL | % |
| ALM_DLY | TIME | — |
| RANGE_HI | REAL | kW |
| ACK | BOOL | — |
Outputs
| Port | Type | Unit |
|---|---|---|
| KW_A | REAL | kW |
| KW_B | REAL | kW |
| KW_TOTAL | REAL | kW |
| KWH_TOTAL | REAL | kWh |
| LOAD_PCT | REAL | % |
| USABLE_KW | REAL | kW |
| VALID | BOOL | — |
| ALM_FEED_A_HI | BOOL | — |
| ALM_FEED_B_HI | BOOL | — |
| ALM_RACK_HI | BOOL | — |
| ALM_NO_REDUND | BOOL | — |
| ALM_FEED_LOST | BOOL | — |
| ALM_METER_FAULT | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
RACK_KW_MON commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 11
- Simulated scans
- 255
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499