RACK_INLET_MON

Three-point rack inlet temperature monitor with ASHRAE banded alarms, top-to-bottom stratification detection and per-sensor fail-over.

Validated application blockDCIM · Racks & ITIEC 61131-3v1.0.0

When to use it

Use RACK_INLET_MON when a rack is instrumented at top, middle and bottom of its cold face and the inlet temperature has to be held inside the ASHRAE thermal envelope, reported to the DCIM layer, and used to detect hot-air recirculation.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
T_TOP_RAWREALdegC
T_MID_RAWREALdegC
T_BOT_RAWREALdegC
TOP_OKBOOL—
MID_OKBOOL—
BOT_OKBOOL—
T_MAXREALdegC
T_WARNREALdegC
DBREALK
STRAT_MAXREALK
ALM_DLYTIME—
RANGE_LOREALdegC
RANGE_HIREALdegC
ACKBOOL—

Outputs

PortTypeUnit
T_TOPREALdegC
T_MIDREALdegC
T_BOTREALdegC
T_WORSTREALdegC
T_STRATREALK
VALIDBOOL—
N_OKUSINTsensors
ALM_WARNBOOL—
ALM_HIBOOL—
ALM_STRATBOOL—
ALM_SENSOR_FAULTBOOL—
ALM_NO_MEASBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
9
Simulated scans
140
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download RACK_INLET_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.