PROT_50_51

ANSI 50/51: a definite-time high set and an IEC 60255-151 inverse-time stage with a selectable reset characteristic.

Validated application blockGen · ProtectionIEC 61131-3IEC 61499v1.0.0

When to use it

Use PROT_50_51 when a generator, incomer or feeder needs a two-stage overcurrent element — an inverse-time stage that grades with the devices downstream and a high-set stage that clears a close-in fault without waiting for the curve.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
IREALA
I_OKBOOL
I_NOMREALA
I50_XREAL×In
I51_XREAL×In
TMSREAL
CURVEUSINT
CURVE_BREALs
T50TIME
RESET_SREALs
DO_RATIOREALpu
BLKBOOL
ACKBOOL

Outputs

PortTypeUnit
PICKUPBOOL
PICKUP_50BOOL
PICKUP_51BOOL
TRIPBOOL
T_TRIPTIME
T_REMAINTIME
T_TRIP_VALIDBOOL
ACC_PCTREAL%
I_MULTREALpu
BLOCKEDBOOL
ALM_MEAS_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

PROT_50_51 commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
13
Simulated scans
510
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download PROT_50_51 — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.