PRIMARY_FREQ_CTRL

Primary frequency control: governor-style droop with a settable deadband, response limit and actuator lag, for islanded operation.

Validated application blockMG · Frequency & DRIEC 61131-3IEC 61499v1.0.0

When to use it

Use PRIMARY_FREQ_CTRL when a dispatchable unit — genset, CHP, grid-forming inverter — must share load with other units in an island by drooping its output against frequency, rather than holding a fixed setpoint.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
FREQREALHz
FREQ_OKBOOL
F_NOMREALHz
DROOP_PCTREAL%
DEADBAND_HZREALHz
P_RATEDREALkW
DP_MAX_PCTREAL%
TAU_SREALs
ACKBOOL

Outputs

PortTypeUnit
DELTA_PREALkW
DELTA_P_RAWREALkW
ACTIVEBOOL
AT_LIMITBOOL
VALIDBOOL
ALM_FREQ_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
355
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499