PRESSURE_DIFF_MON

Differential-pressure monitor for aisle containment, filters and room pressurisation, with zero trim, band alarms and airflow-reversal latch.

Validated application blockDCIM · EnvironmentIEC 61131-3IEC 61499v1.0.0

When to use it

Use PRESSURE_DIFF_MON when a differential pressure has to be held inside a band — cold aisle to hot aisle across containment, across a filter bank, or a room against its surroundings — and both the loss of that differential and its reversal have to be annunciated.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
DP_RAWREALPa
SENSOR_OKBOOL
DP_ZERO_PAREALPa
LOREALPa
HIREALPa
HYST_PAREALPa
REV_PAREALPa
FILT_TTIME
ALM_DLYTIME
ACKBOOL

Outputs

PortTypeUnit
DP_PAREALPa
OKBOOL
CONTAINMENT_OKBOOL
DP_LOWBOOL
DP_HIGHBOOL
ALM_DP_LOWBOOL
ALM_DP_HIGHBOOL
ALM_REVERSEDBOOL
ALM_SENSOR_FAULTBOOL
ALM_CFG_ERRBOOL
VALIDBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
135
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499