OUTDOOR_WEATHER

Outdoor air conditions for economiser decisions: filtered dry bulb, Stull wet bulb, dew point and a hysteretic free-cooling / evaporative mode.

Validated application blockDCIM · EnvironmentIEC 61131-3IEC 61499v1.0.0

When to use it

Use OUTDOOR_WEATHER when a data centre's cooling plant chooses between mechanical cooling, evaporative or adiabatic assist and full free cooling on outdoor conditions, and that choice must not flip on a gust or on a failed outdoor sensor.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
OAT_RAWREAL°C
RH_RAWREAL%
SENSOR_OKBOOL
FILT_TTIME
ECON_T_CREAL°C
ECON_WB_CREAL°C
MODE_HYST_KREALK
T_RANGE_LO_CREAL°C
T_RANGE_HI_CREAL°C
ACKBOOL

Outputs

PortTypeUnit
OATREAL°C
OAT_WBREAL°C
RHREAL%
OAT_DPREAL°C
MODEUSINT
FREE_COOL_OKBOOL
EVAP_OKBOOL
ALM_SENSOR_FAULTBOOL
ALM_WB_CALCBOOL
VALIDBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
8
Simulated scans
1586
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499