ODOR_H2S_MON

Hydrogen-sulphide odour monitoring with scrubber call, minimum run time, exposure dose and latched high-level alarm.

Validated application blockW/WW · CollectionIEC 61131-3IEC 61499v1.0.0

When to use it

Use ODOR_H2S_MON when a wet well, rising-main discharge chamber, inlet works or covered channel is monitored for H2S, and a chemical or biological odour scrubber is called on when the headspace concentration rises.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
PPMREALppm
PPM_OKBOOL
PPM_HIREALppm
PPM_DBREALppm
PPM_HHREALppm
MIN_RUNTIME
POST_RUNTIME
SCRUB_AVAILBOOL
ACKBOOL

Outputs

PortTypeUnit
SCRUB_CALLBOOL
H2S_HIGHBOOL
PEAK_PPMREALppm
DOSE_PPM_HLREALppm.h
SCRUB_HREALh
SENSOR_VALIDBOOL
ALM_H2S_HHBOOL
ALM_SENSORBOOL
ALM_NO_SCRUBBERBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
414
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download ODOR_H2S_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.