LYO_ENDPOINT_DET

Primary-drying endpoint by comparative pressure: arms on proven Pirani/capacitance divergence, then requires sustained, filtered convergence.

Validated application blockLS · LyophilizationIEC 61131-3IEC 61499v1.0.0

When to use it

Use LYO_ENDPOINT_DET when primary drying is ended on comparative pressure measurement — a Pirani gauge alongside a capacitance manometer — instead of on a fixed time, and declaring the endpoint early would leave ice in the cake.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
RUNBOOL
PIRANIREALPa
CM_BARATRONREALPa
CONVERGE_PCTREAL%
PIRANI_OKBOOL
CM_OKBOOL
ARM_RATIOREALratio
ARM_TIMETIME
FILT_SREALs
CONF_TIMETIME
P_MINREALPa
MAX_TIMETIME
ACKBOOL

Outputs

PortTypeUnit
CONVERGEDBOOL
RATIOREALratio
DIFF_PCTREAL%
ARMEDBOOL
ELAPSED_SREALs
ENDPOINT_SREALs
VALIDBOOL
ALM_NO_ENDPOINTBOOL
ALM_GAUGE_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
558
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download LYO_ENDPOINT_DET — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.