LOAD_RESTORE_SEQ

Staged load restoration: one block at a time, each gated on generation headroom and on frequency holding stable for a dwell, with a back-off on instability.

Validated application blockMG · Frequency & DRIEC 61131-3IEC 61499v1.0.0

When to use it

Use LOAD_RESTORE_SEQ when an island has been stabilised by shedding and load must be put back in blocks — never all at once — with the frequency response to each block proving the machines can carry the next one.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
STARTBOOL
HOLDBOOL
ABORTBOOL
FREQREALHz
FREQ_OKBOOL
F_MINREALHz
STABLE_TTIME
BLOCK_KWREALkW
N_BLOCKSUSINT
HEADROOM_KWREALkW
MARGIN_KWREALkW
ACKBOOL

Outputs

PortTypeUnit
BLOCKUSINT
BLOCK_ONBOOL
RESTORED_KWREALkW
DONEBOOL
DWELLINGBOOL
HOLDINGBOOL
ALM_UNSTABLEBOOL
ALM_NO_HEADROOMBOOL
ALM_FREQ_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
286
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download LOAD_RESTORE_SEQ — free