LEVEL_RADAR

Non-contact radar level conditioning with distance-mode conversion, echo-loss hold, slew limiting and NAMUR signal supervision.

Validated application blockW/WW · Flow & HydraulicsIEC 61131-3IEC 61499v1.0.0

When to use it

Use LEVEL_RADAR when a non-contact radar gauge measures level in a wet well, reservoir, storm tank or sludge holding tank, and brief echo losses from foam, turbulence or a passing scraper must not propagate into the control logic as a level step.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
RAW_MAREALmA
LRVREALm
URVREALm
DIST_MODEBOOL
REF_HEIGHT_MREALm
ECHO_INBOOL
HOLD_TMOTIME
MAX_RATE_M_SREALm/s
ACKBOOL

Outputs

PortTypeUnit
LEVELREALm
LEVEL_PCTREAL%
ECHO_OKBOOL
VALIDBOOL
HOLDINGBOOL
ALM_ECHO_LOSTBOOL
ALM_SIG_FAULTBOOL
ALM_SLEW_LIMBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
397
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download LEVEL_RADAR — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.