IT_SHED_COORD

Two-stage graceful IT load-shed coordinator with measured achievement, grace-period escalation to a forced shed, and one-stage-at-a-time restoration.

Validated application blockDCIM · Racks & ITIEC 61131-3v1.0.0

When to use it

Use IT_SHED_COORD when a hall must remove IT load on demand — utility lost and the generator cannot carry the full block, a cooling failure with minutes of thermal ride-through, or a UPS on battery — and the shed is executed by an orchestration layer that needs to be told how much to remove and given time to do it gracefully.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
SHED_1BOOL—
SHED_2BOOL—
RESTOREBOOL—
STAGE1_KWREALkW
STAGE2_KWREALkW
GRACETIME—
IT_KWREALkW
TOL_KWREALkW
ALLOW_FORCEBOOL—
STABLEBOOL—
RESTORE_HOLDTIME—
ACKBOOL—

Outputs

PortTypeUnit
SHED_KWREALkW
STAGEUSINTstage
SHED_REQBOOL—
FORCE_REQBOOL—
ACHIEVED_KWREALkW
DONEBOOL—
FAILBOOL—
RESTORE_PERMITBOOL—
ALM_SHED_FAILBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
13
Simulated scans
297
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.