INTRUSION_MON

Four-zone intrusion monitor with exit and entry delays, first-up zone capture and an always-live tamper loop.

Validated application blockDCIM · SecurityIEC 61131-3IEC 61499v1.0.0

When to use it

Use INTRUSION_MON when a plant room, meet-me room, cage or perimeter is protected by supervised door contacts and motion detectors that have to be armed out of hours, with one authorised entry route the operator uses to reach the keypad.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortType
PARAMSSTRING
ENABLEBOOL
ARMEDBOOL
Z1_SECUREBOOL
Z2_SECUREBOOL
Z3_SECUREBOOL
Z4_SECUREBOOL
ZONES_USEDUSINT
ENTRY_ZONEUSINT
TAMPER_OKBOOL
EXIT_DLYTIME
ENTRY_DLYTIME
ACKBOOL

Outputs

PortType
ZONEUSINT
BREACHBOOL
ZONE_FIRSTUSINT
ZONES_OPENUSINT
ENTRY_ACTIVEBOOL
EXIT_ACTIVEBOOL
READY_TO_ARMBOOL
ALM_TAMPERBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
1393
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download INTRUSION_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.