HW_RESET_CTRL

Hot-water supply-temperature outdoor-air reset schedule with a rate-limited setpoint.

Validated application blockBAS · Central PlantIEC 61131-3IEC 61499v1.0.0

When to use it

Use HW_RESET_CTRL when a hot-water plant, a heating zone or a radiant loop needs its supply setpoint scheduled against outdoor air, independently of whatever stages the heat source.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
OA_TEMPREAL°C
OA_OKBOOL
OA_LOWREAL°C
OA_HIGHREAL°C
SP_MAXREAL°C
SP_MINREAL°C
RATE_K_MINREALK/min

Outputs

PortTypeUnit
HW_SPREAL°C
VALIDBOOL
ALM_OA_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
116
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download HW_RESET_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.