HTST_DIVERT_VALVE

Flow diversion device with dual-probe agreement, hold-tube residence proving, seat proving and a forward-flow interlock.

Validated application blockF&B · ThermalIEC 61131-3IEC 61499v1.0.0

When to use it

Use HTST_DIVERT_VALVE when an HTST flow diversion device is driven from two independent temperature probes and its seat position is proved by limit switches, so a probe disagreement, an unproven hold tube or a valve that does not travel must force and hold the divert position.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
PROD_TREAL°C
PROD_T_BREAL°C
DUAL_PROBE_OKBOOL
CUTIN_TREAL°C
MAX_DEV_KREALK
HOLD_TTIME
FLOW_PERMITBOOL
LS_FWDBOOL
LS_DIVBOOL
TRAVEL_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
FWD_FLOWBOOL
DIVERTEDBOOL
VALVE_POSUSINT
HOLD_PROVENBOOL
PROBE_DEV_KREALK
ALM_PROBE_DEVBOOL
ALM_VALVE_FAILBOOL
ALM_UNDER_TEMPBOOL
ALM_PROBE_FAULTBOOL
ALM_NO_PERMITBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
8
Simulated scans
144
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499