GAS_MIX_MFC

Four-gas mass-flow-controller blending with a vvm cap, proportional scale-back and an oxygen-fraction limit.

Validated application blockLS · BioreactorIEC 61131-3IEC 61499v1.0.0

When to use it

Use GAS_MIX_MFC when air, oxygen, carbon dioxide and nitrogen are metered into one sparger or overlay by separate mass-flow controllers, and the total flow and the delivered oxygen fraction both have to be bounded no matter what the upstream loops ask for.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
AIR_SPREALslpm
O2_SPREALslpm
CO2_SPREALslpm
N2_SPREALslpm
VOLUME_LREALL
VOL_OKBOOL
TOTAL_MAX_VVMREALvvm
TOTAL_MAX_SLPMREALslpm
O2_FRAC_MAXREAL-

Outputs

PortTypeUnit
TOTAL_VVMREALvvm
AIR_CMDREALslpm
O2_CMDREALslpm
CO2_CMDREALslpm
N2_CMDREALslpm
TOTAL_SLPMREALslpm
O2_FRACREAL-
SCALEDBOOL
VALIDBOOL
ALM_FLOW_LIMITBOOL
ALM_O2_LIMITBOOL
ALM_VOL_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
30
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download GAS_MIX_MFC — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.