FAN_COIL_CTRL
Fan-coil unit control — three-speed fan staging, modulating coil valve, changeover-water interlock and coil purge.
When to use it
Use FAN_COIL_CTRL when a room is served by a fan-coil unit or a chilled-beam-style terminal with a three-speed fan and one modulating coil valve, and the water in that coil is heating or chilled depending on what the central plant is doing.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| ENABLE | BOOL | — |
| ZONE_TEMP | REAL | degC |
| TEMP_OK | BOOL | — |
| ZONE_SP | REAL | degC |
| OCC | BOOL | — |
| DEADBAND_K | REAL | K |
| SETBACK_K | REAL | K |
| SP_PRESETBACK | BOOL | — |
| HEAT_MODE | BOOL | — |
| P_BAND_K | REAL | K |
| TI_S | REAL | s |
| SPD1_PCT | REAL | % |
| SPD2_PCT | REAL | % |
| SPD3_PCT | REAL | % |
| SPD_HYST_PCT | REAL | % |
| FAN_MIN_OCC | BOOL | — |
| PURGE_TMO | TIME | — |
| DEV_K | REAL | K |
| DEV_TMO | TIME | — |
| ACK | BOOL | — |
Outputs
| Port | Type | Unit |
|---|---|---|
| FAN_SPEED | USINT | — |
| VLV | REAL | % |
| MODE | USINT | — |
| VALID | BOOL | — |
| ALM_WRONG_WATER | BOOL | — |
| ALM_COMFORT_DEV | BOOL | — |
| ALM_SENSOR | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Validation evidence
- Tests
- 13
- Simulated scans
- 214
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499
Download FAN_COIL_CTRL — free
Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.
Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.
Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.