EXPORT_LIMIT_GUARD

Zero or limited export enforcement: derives a rate-limited generation ceiling from the measured tie flow before the export limit is reached.

Validated application blockMG · PCC & ProtectionIEC 61131-3IEC 61499v1.0.0

When to use it

Use EXPORT_LIMIT_GUARD when an interconnection agreement caps how much power may leave the site — commonly at zero — and on-site generation has to be curtailed to stay under that cap rather than tripped when it is exceeded.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
TIE_KWREALkW
GEN_KWREALkW
MEAS_OKBOOL
EXPORT_LIMITREALkW
MARGINREALkW
RELEASE_KWREALkW
GEN_MAX_KWREALkW
SAFE_LIMIT_KWREALkW
RAMP_DN_PCT_SREAL%/s
RAMP_UP_PCT_SREAL%/s
OVER_TTIME
ACKBOOL

Outputs

PortTypeUnit
CURTAILBOOL
GEN_LIMIT_KWREALkW
LIMIT_PCTREAL%
EXPORT_KWREALkW
OVER_KWREALkW
VALIDBOOL
ALM_OVER_LIMITBOOL
ALM_OOSBOOL
ALM_MEAS_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
146
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download EXPORT_LIMIT_GUARD — free