ENGINE_PROTECT
Engine shutdowns for low oil pressure, high coolant temperature and overspeed, with a start inhibit and a first-out cause code.
When to use it
Use ENGINE_PROTECT when a generator set needs its engine shutdowns implemented in the controller — low lube-oil pressure, high jacket-water temperature and overspeed — with the shutdown latched and the reason it tripped preserved for the operator.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| RUNNING | BOOL | — |
| OIL_P | REAL | bar |
| OIL_OK | BOOL | — |
| COOL_T | REAL | degC |
| TEMP_OK | BOOL | — |
| RPM | REAL | rpm |
| RPM_OK | BOOL | — |
| OIL_MIN | REAL | bar |
| OIL_WARN | REAL | bar |
| TEMP_MAX | REAL | degC |
| TEMP_WARN | REAL | degC |
| OSPD_RPM | REAL | rpm |
| OIL_DLY | TIME | — |
| TEMP_DLY | TIME | — |
| SAFETY_ON_T | TIME | — |
| OSPD_DLY | TIME | — |
| FAULT_DLY | TIME | — |
| RUN_DEB_T | TIME | — |
| DISARM_ALM_T | TIME | — |
| OIL_HYST | REAL | bar |
| TEMP_HYST | REAL | degC |
| TRIP_ON_FAULT | BOOL | — |
| ACK | BOOL | — |
Outputs
| Port | Type |
|---|---|
| TRIP | BOOL |
| CAUSE | USINT |
| WARN | BOOL |
| ARMED | BOOL |
| ALM_LOW_OIL | BOOL |
| ALM_HIGH_TEMP | BOOL |
| ALM_OVERSPEED | BOOL |
| ALM_SENSOR_FAULT | BOOL |
| ALM_UNARMED | BOOL |
| ALM_CFG_ERR | BOOL |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
ENGINE_PROTECT commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 15
- Simulated scans
- 401
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499