DELTA_T_MON

Rack and CRAH air-side delta-T monitor: low-delta bypass syndrome, latched airflow loss, and a reversed-sensor check.

Validated application blockDCIM · CoolingIEC 61131-3v1.0.0

When to use it

Use DELTA_T_MON when supply and return air temperatures are measured across a CRAH or a rack row and the site needs to know whether the air is doing its job — low delta-T meaning bypass or recirculation, high delta-T meaning the airflow has gone.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
T_SUPPLYREALdegC
T_RETURNREALdegC
T_OKBOOL—
DT_MINREALK
DT_MAXREALK
HYST_KREALK
CONFIRMTIME—
REV_LIMITREALK
ACKBOOL—

Outputs

PortTypeUnit
DTREALK
LOW_DTBOOL—
HIGH_DTBOOL—
VALIDBOOL—
ALM_AIRFLOW_LOSSBOOL—
ALM_SENSOR_REVBOOL—
ALM_T_FAULTBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
7
Simulated scans
187
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download DELTA_T_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.