DELTA_T_MON

Rack and CRAH air-side delta-T monitor: low-delta bypass syndrome, latched airflow loss, and a reversed-sensor check.

Validated application blockDCIM · CoolingIEC 61131-3IEC 61499v1.0.0

When to use it

Use DELTA_T_MON when supply and return air temperatures are measured across a CRAH or a rack row and the site needs to know whether the air is doing its job — low delta-T meaning bypass or recirculation, high delta-T meaning the airflow has gone.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
T_SUPPLYREALdegC
T_RETURNREALdegC
T_OKBOOL
DT_MINREALK
DT_MAXREALK
HYST_KREALK
CONFIRMTIME
REV_LIMITREALK
ACKBOOL

Outputs

PortTypeUnit
DTREALK
LOW_DTBOOL
HIGH_DTBOOL
VALIDBOOL
ALM_AIRFLOW_LOSSBOOL
ALM_SENSOR_REVBOOL
ALM_T_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
187
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DELTA_T_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.