DEAD_BUS_CLOSE

Dead-bus closing permissive with a broadcast claim and single-closer arbitration interlock.

Validated application blockGen · SynchronizationIEC 61131-3IEC 61499v1.0.0

When to use it

Use DEAD_BUS_CLOSE when the first generator onto a de-energised bus must close without synchronising, and several sets could each be first — so exactly one of them may claim the dead bus and the rest must be held off.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
CLOSE_REQBOOL
BUS_VREALpu
DEAD_V_MAXREALpu
LIVE_PUREALpu
GEN_VREALpu
GEN_FREALHz
F_NOMREALHz
F_TOLREALHz
MEAS_OKBOOL
ARBITRATION_OKBOOL
PEER_CLAIMBOOL
SRC_PRIOUINT
PEER_PRIOUINT
CB_CLOSEDBOOL
DEAD_TTIME
CLAIM_TMOTIME
ACKBOOL

Outputs

PortType
OKBOOL
CLAIMBOOL
BUS_DEADBOOL
BUS_LIVEBOOL
SRC_READYBOOL
ALM_BUS_LIVEBOOL
ALM_ARBITRATIONBOOL
ALM_CLAIM_TMOBOOL
ALM_MEAS_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
134
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DEAD_BUS_CLOSE — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.