DCW_TANK_LEVEL_CTRL

Storage / break-tank fill control with source interlock and downstream dry-run protection.

Validated application blockDC-WTP · Makeup & LevelIEC 61131-3IEC 61499v1.0.0

When to use it

Use DCW_TANK_LEVEL_CTRL when a break tank, treated-water tank, or reclaim tank is filled from an upstream source on level, and the pumps taking suction from that tank must be inhibited before it runs dry.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
LEVEL_PCTREAL%
LVL_OKBOOL
SRC_AVAILBOOL
FILL_ON_PCTREAL%
FILL_OFF_PCTREAL%
LO_LO_PCTREAL%
RESTART_BAND_PCTREAL%
HI_HI_PCTREAL%
FILL_TMOTIME
ACKBOOL

Outputs

PortType
FILL_CMDBOOL
DRY_RUN_INHIBITBOOL
LEVEL_LOWBOOL
ALM_OVERFLOWBOOL
ALM_NO_SOURCEBOOL
ALM_FILL_TMOBOOL
ALM_LVL_FAULTBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

DCW_TANK_LEVEL_CTRL commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
6
Simulated scans
57
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DCW_TANK_LEVEL_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.