DCW_SIDESTREAM_FILTER

Side-stream / basin-sweeper filter supervision with a three-criterion backwash request and header lockout.

Validated application blockDC-WTP · Filtration & SofteningIEC 61131-3IEC 61499v1.1.0

When to use it

Use DCW_SIDESTREAM_FILTER when a cooling-tower basin is kept swept by a side-stream sand, multimedia or screen filter that has to be backwashed periodically, and the wash has to be requested rather than started — because several filters share one backwash header.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
RUN_PERMITBOOL—
FLOWREALm3/h
FLOW_OKBOOL—
MIN_FLOWREALm3/h
FLOW_HYSTREALm3/h
DP_BARREALbar
DP_OKBOOL—
DP_TRIP_BARREALbar
DP_RESET_BARREALbar
DP_HIGH_BARREALbar
DP_FILT_TTIME—
DP_ARM_TTIME—
RUNTIME_LIMITTIME—
VOLUME_LIMIT_M3REALm3
FLOW_FAIL_TTIME—
CLEAN_PROOF_TTIME—
LOCKOUTBOOL—
WASH_ACTIVEBOOL—
WASH_DONEBOOL—
ACKBOOL—

Outputs

PortTypeUnit
FILTER_RUN_CMDBOOL—
IN_SERVICEBOOL—
BW_REQUESTBOOL—
REQ_BY_DPBOOL—
REQ_BY_TIMEBOOL—
REQ_BY_VOLUMEBOOL—
SERVICE_HREALh
SERVICE_VOL_M3REALm3
LOAD_PCTREAL%
WASH_COUNTDINT—
ALM_DP_HIGHBOOL—
ALM_DP_FAULTBOOL—
ALM_FLOW_FAULTBOOL—
ALM_NO_FLOWBOOL—
ALM_WASH_INEFFBOOL—
ALM_NO_CRITERIONBOOL—
ALM_CFG_ERRBOOL—

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

DCW_SIDESTREAM_FILTER commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
17
Simulated scans
523
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499