DCW_LEGIONELLA_FLUSH
Dead-leg / low-use branch flush scheduler with proven-flow verification and days-since-flush compliance reporting.
When to use it
Use DCW_LEGIONELLA_FLUSH when a low-use or dead-leg branch — a standby tower cell, a seasonal makeup line, a redundant filter train, an infrequently-used drain-down or sample line — has to be flushed on a schedule or on measured stagnation, and the flush has to be evidenced rather than merely commanded.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| ENABLE | BOOL | — |
| START_REQ | BOOL | — |
| INHIBIT | BOOL | — |
| FLOW_LPM | REAL | L/min |
| FLOW_OK | BOOL | — |
| LEG_FLOW_OK | BOOL | — |
| TEMP_C | REAL | degC |
| TEMP_FITTED | BOOL | — |
| MIN_FLOW_LPM | REAL | L/min |
| MIN_TEMP_C | REAL | degC |
| FLUSH_DUR | TIME | — |
| FLUSH_TMO | TIME | — |
| INTERVAL_H | REAL | h |
| MAX_STAG_H | REAL | h |
| OVERDUE_H | REAL | h |
| RETRY_H | REAL | h |
| ACK | BOOL | — |
Outputs
| Port | Type | Unit |
|---|---|---|
| FLUSH_CMD | BOOL | — |
| FLOW_PROVEN | BOOL | — |
| TEMP_PROVEN | BOOL | — |
| FLUSH_PROG_S | REAL | s |
| H_SINCE_FLUSH | REAL | h |
| D_SINCE_FLUSH | REAL | d |
| H_STAGNANT | REAL | h |
| FLUSH_COUNT | DINT | — |
| FLUSH_DUE | BOOL | — |
| OVERDUE | BOOL | — |
| ALM_FLUSH_FAIL | BOOL | — |
| ALM_DEV_FAULT | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
DCW_LEGIONELLA_FLUSH commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 10
- Simulated scans
- 405
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499
Download DCW_LEGIONELLA_FLUSH — free
Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.
Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.
Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.