DCW_CONDENSATE_RECOVERY

Condensate / reclaim sump transfer with quality-gated divert, stagnation refresh and recovery totalising.

Validated application blockDC-WTP · Reuse, Hygiene & MetricsIEC 61131-3IEC 61499v1.1.0

When to use it

Use DCW_CONDENSATE_RECOVERY when air-handler condensate, blowdown reclaim or harvested rainwater is collected in a sump and transferred to a makeup or break tank, and off-spec water must be diverted to drain rather than admitted to the treated inventory.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
SUMP_PCTREAL%
LVL_OKBOOL—
COND_USREALuS/cm
COND_OKBOOL—
COND_MIN_USREALuS/cm
TURB_NTUREALNTU
TURB_FITTEDBOOL—
COND_MAX_USREALuS/cm
COND_HYST_USREALuS/cm
TURB_MAX_NTUREALNTU
START_PCTREAL%
STOP_PCTREAL%
HIGH_PCTREAL%
DEST_AVAILBOOL—
DIVERT_PUMPEDBOOL—
STAG_TMOTIME—
DUMP_DURTIME—
XFER_TMOTIME—
XFER_FLOWREALm3/h
MAKEUP_FLOWREALm3/h
MIN_REF_M3REALm3
ACKBOOL—

Outputs

PortTypeUnit
PUMP_CMDBOOL—
XFER_CMDBOOL—
DIVERT_CMDBOOL—
QUALITY_OKBOOL—
STAG_DUMPBOOL—
RECOVERED_M3REALm3
DIVERTED_M3REALm3
DUMPED_M3REALm3
RECOVERY_PCTREAL%
RECOVERY_VALIDBOOL—
ALM_QUALITYBOOL—
ALM_RECLAIM_LOSTBOOL—
ALM_XFER_TMOBOOL—
ALM_INST_FAULTBOOL—
ALM_CFG_ERRBOOL—

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

DCW_CONDENSATE_RECOVERY commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
19
Simulated scans
365
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DCW_CONDENSATE_RECOVERY — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.