DCV_CTRL

Demand-controlled ventilation — differential-CO2 outdoor-air reset between the base minimum and the design maximum, rate-limited and failing to MAXIMUM.

Validated application blockBAS · Air HandlingIEC 61131-3IEC 61499v1.0.0

When to use it

Use DCV_CTRL when a zone or air-handling unit varies its outdoor-air rate with occupancy inferred from CO2, between a base building ventilation minimum and a design-occupancy maximum, per the ASHRAE 62.1 ventilation-rate procedure.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
OCCBOOL
ZONE_CO2REALppm
CO2_OKBOOL
CO2_SPREALppm
OA_CO2REALppm
PROP_BANDREALppm
MIN_OAREALl/s
MAX_OAREALl/s
MIN_OA_UNOCCREALl/s
RAMP_RATEREALl/s per s
HI_ALM_PPMREALppm
ACKBOOL

Outputs

PortTypeUnit
OA_FLOW_SPREALl/s
DEMAND_PCTREAL%
VALIDBOOL
ALM_CO2_HIGHBOOL
ALM_CO2_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
11
Simulated scans
151
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DCV_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.