DAMPER_CTRL

Ventilation damper position control with a rate-limited command, feedback proving on a travel timeout, and a commanded fire position.

Validated application blockTransit · Tunnel VentilationIEC 61131-3IEC 61499v1.0.0

When to use it

Use DAMPER_CTRL when a modulating tunnel ventilation damper, louvre or smoke damper is driven to a position and must be proved there by its own feedback, with a defined position for fire mode and a defined position when the control is not in service.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
FIRE_MODEBOOL
CMD_PCTREAL%
POS_FBREAL%
POS_OKBOOL
FIRE_POS_PCTREAL%
FAIL_POS_PCTREAL%
SLEW_PCT_SREAL%/s
POS_TOLREAL%
TRAVEL_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
DAMPER_PCTREAL%
FAILEDBOOL
TARGET_PCTREAL%
AT_POSBOOL
MOVINGBOOL
POS_ERRREAL%
VALIDBOOL
ALM_POS_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
264
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download DAMPER_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.