CW_PUMP_VFD_CTRL

Chilled-water pump VFD speed control on loop differential pressure, with a minimum-speed floor and an affinity-law power estimate.

Validated application blockDCIM · CoolingIEC 61131-3IEC 61499v1.0.0

When to use it

Use CW_PUMP_VFD_CTRL when a variable-speed chilled-water pump holds a differential pressure across the distribution loop, the drive must not be taken below the speed at which the pump makes head or the chillers lose minimum flow, and the loop must never be allowed to stop because a transmitter died.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
DP_SPREALkPa
DP_PVREALkPa
DP_OKBOOL
SPD_MINREAL%
SPD_MAXREAL%
KPREAL%/kPa
TIREALs
RATED_KWREALkW
FAIL_SPD_PCTREAL%
LOW_DP_DEVREALkPa
LOW_DP_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
SPEED_PCTREAL%
KWREALkW
AT_MAXBOOL
VALIDBOOL
ALM_DP_FAULTBOOL
ALM_DP_LOWBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
6
Simulated scans
3175
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CW_PUMP_VFD_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.