CWS_TEMP_RESET

Chilled-water supply temperature reset from the worst-case coil valve position, rate-limited and clamped, failing to the coldest setpoint.

Validated application blockDCIM · CoolingIEC 61131-3IEC 61499v1.0.0

When to use it

Use CWS_TEMP_RESET when a chilled-water plant serves coils whose valve positions are polled, and the supply temperature should be raised for plant efficiency only as far as the most-open valve allows.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
VALVE_MAX_PCTREAL%
VALVE_OKBOOL
VALVE_PLAUS_LOREAL%
SP_MINREALdegC
SP_MAXREALdegC
VALVE_HI_PCTREAL%
VALVE_LO_PCTREAL%
RATE_K_PER_MINREALK/min
HOLDBOOL
NO_CAP_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
CWS_SPREALdegC
RESETTINGBOOL
AT_MINBOOL
AT_MAXBOOL
ALM_NO_CAPACITYBOOL
ALM_VALVE_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
8
Simulated scans
1046
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CWS_TEMP_RESET — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.