CRAC_DX_CTRL

DX CRAC compressor staging on return-air temperature with anti-cycle protection and a supply-air low limit.

Validated application blockDCIM · CoolingIEC 61131-3IEC 61499v1.0.0

When to use it

Use CRAC_DX_CTRL when a direct-expansion computer-room air conditioner cools on return-air temperature with one or more compressor stages, and the compressors must be protected from short-cycling and the coil from being driven to its low limit.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
RAT_PVREALdegC
RAT_OKBOOL
SAT_PVREALdegC
SAT_OKBOOL
RAT_SPREALdegC
STAGESUSINT
UP_DBREALK
DN_DBREALK
STAGE_DLYTIME
SAT_LO_LIMITREALdegC
SAT_LO_DLYTIME
FAIL_STAGESUSINT
HI_DEVREALK
HI_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
STAGE_ONUSINT
SATREALdegC
AT_CAPACITYBOOL
ALM_T_FAULTBOOL
ALM_SAT_LOWBOOL
ALM_HIGH_RATBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
492
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CRAC_DX_CTRL — free