COOLING_TOWER_CTRL

Cooling-tower cell staging on condenser-water temperature with equal-speed sharing across running cells and a low-limit cut-out.

Validated application blockDCIM · CoolingIEC 61131-3v1.0.0

When to use it

Use COOLING_TOWER_CTRL when a multi-cell cooling tower with variable-speed fans holds condenser-water supply temperature for a chiller plant, and the condenser water must not be driven below the chillers' minimum entering temperature.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
CWT_PVREALdegC
CWT_OKBOOL—
CWT_SPREALdegC
N_CELLSUSINT—
KPREAL%/K
TIREALs
SPD_MINREAL%
LOW_LIMITREALdegC
UP_HYSTREALcells
DN_HYSTREALcells
STAGE_DLYTIME—
FAIL_FAN_PCTREAL%
HI_DEVREALK
HI_TMOTIME—
ACKBOOL—

Outputs

PortTypeUnit
FANS_ONUSINT—
SPEED_PCTREAL%
DEMAND_PCTREAL%
ALM_CWT_FAULTBOOL—
ALM_LOW_CWTBOOL—
ALM_HIGH_CWTBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
7
Simulated scans
312
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download COOLING_TOWER_CTRL — free