CONDENSER_WATER_CTRL

Condenser-water loop control: load-following pump speed and a tower-bypass loop that holds the minimum entering-water temperature.

Validated application blockBAS · Central PlantIEC 61131-3IEC 61499v1.0.0

When to use it

Use CONDENSER_WATER_CTRL when a condenser-water loop runs variable flow against chiller load and needs a tower bypass to stop the water arriving colder than the chiller can use, typically in winter or at low load.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
CW_SUPREAL°C
CW_OKBOOL
CW_SPREAL°C
LOADREAL%
LOAD_OKBOOL
KPREAL%/K
TITIME
SPD_MINREAL%
FAIL_SPEEDREAL%
BYPASS_FAIL_PCTREAL%
LO_DBREALK
LO_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
PUMP_SPEEDREAL%
TOWER_BYPASSREAL%
VALIDBOOL
ALM_CW_LOWBOOL
ALM_SENSORBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
6
Simulated scans
469
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CONDENSER_WATER_CTRL — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.