CONDENSER_TEMP_MON

Condenser coil temperature monitor: capacity permissive with hysteresis, ice-load rate-of-rise trend and a latched overload.

Validated application blockLS · LyophilizationIEC 61131-3IEC 61499v1.0.0

When to use it

Use CONDENSER_TEMP_MON when the ice condenser of a freeze dryer must be proved cold enough to keep taking the sublimation load before and during primary drying, and its coil temperature is the only measurement of that capacity.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
TREALdegC
MAX_CREALdegC
T_OKBOOL
WARN_CREALdegC
HYST_CREALdegC
TMOTIME
TREND_SREALs
RISE_LIMITREALdegC/min
ACKBOOL

Outputs

PortTypeUnit
OKBOOL
T_VALIDBOOL
COIL_TREALdegC
TREND_C_MINREALdegC/min
WARNBOOL
ALM_HIGHBOOL
ALM_OVERLOADBOOL
ALM_RISINGBOOL
ALM_T_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
8
Simulated scans
264
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CONDENSER_TEMP_MON — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.