CLEANROOM_PRESS_CASCADE

Cleanroom differential-pressure cascade control with low-DP and cascade-reversal protection.

Validated application blockLS · EnvironmentIEC 61131-3IEC 61499v1.0.0

When to use it

Use CLEANROOM_PRESS_CASCADE when a classified room, airlock or change room is held at a differential pressure to the space next to it by a modulating supply or extract damper, and the direction of that cascade is a licence commitment that may never reverse.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
ROOM_DPREALPa
DP_OKBOOL
DP_SPREALPa
DP_MINREALPa
DP_MAXREALPa
DP_REVREALPa
BIAS_PCTREAL%
KPREAL%/Pa
TI_SREALs
DLYTIME
DOOR_OPENBOOL
MANBOOL
MAN_PCTREAL%
FAIL_PCTREAL%
ACKBOOL

Outputs

PortTypeUnit
DAMPER_PCTREAL%
CASCADE_OKBOOL
DP_FILTREALPa
ALM_DP_LOWBOOL
ALM_REVERSALBOOL
ALM_DP_HIGHBOOL
ALM_DP_FAULTBOOL
ALM_CFG_ERRBOOL
DP_LOW_MINUTESREALmin
DOOR_MINUTESREALmin

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
11
Simulated scans
1111
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download CLEANROOM_PRESS_CASCADE — free