CHILLER_SEQ

Chiller plant staging on measured load with a look-ahead stage-down test and an anti-cycle delay.

Validated application blockDCIM · CoolingIEC 61131-3v1.0.0

When to use it

Use CHILLER_SEQ when a chilled-water plant of equally sized machines must add and shed chillers on measured plant load without hunting, and the last machine must not be allowed to stop under a data hall that still needs cooling.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
PLANT_KWREALkW
KW_OKBOOL—
CAP_PER_CHILLERREALkW
N_AVAILUSINT—
UP_PCTREAL%
DN_PCTREAL%
DELAYTIME—
MIN_LOAD_KWREALkW
PULSE_TTIME—
ACKBOOL—

Outputs

PortTypeUnit
N_RUNUSINT—
STAGE_UPBOOL—
STAGE_DNBOOL—
LOAD_PCTREAL%
VALIDBOOL—
ALM_NO_CAPACITYBOOL—
ALM_NO_AVAILBOOL—
ALM_KW_FAULTBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
9
Simulated scans
386
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download CHILLER_SEQ — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.