CHILLER_PLANT_SEQ

Chiller plant staging on machine loading and chilled-water supply temperature, with anti-short-cycle protection in both directions; lead/lag rotation is NOT in this block.

Validated application blockBAS · Central PlantIEC 61131-3IEC 61499v1.0.0

When to use it

Use CHILLER_PLANT_SEQ when two or more equally sized chillers serve one chilled-water plant and the number of machines running has to follow the cooling load without cycling a compressor — and the run-hour rotation that decides WHICH machines those are is handled by the chiller start logic downstream, not here.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
COOL_REQBOOL
LOAD_TONREALton
LOAD_OKBOOL
CHW_SUPREAL°C
CHW_OKBOOL
CHW_SPREAL°C
N_CHILLERSUSINT
CHILLER_TONREALton
UP_PCTREAL%
DN_PCTREAL%
DB_KREALK
UP_DLYTIME
DN_DLYTIME
MIN_STAGE_TIMETIME
FTM_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
STAGEUSINT
CHILLERS_ONUSINT
NEXT_STAGEBOOL
LOAD_PCTREAL%
VALIDBOOL
ALM_FAIL_TO_MAINTAINBOOL
ALM_SENSORBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
884
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499