CHILLER_FREEZER_CTRL

Spiral or blast freezer refrigeration control, belt residence time and latched cold-chain deviation.

Validated application blockF&B · ThermalIEC 61131-3IEC 61499v1.0.0

When to use it

Use CHILLER_FREEZER_CTRL when a spiral or blast freezer holds an air temperature with modulating refrigeration while product passes on a belt, and a sustained warm excursion has to quarantine product rather than merely alarm.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
TREAL°C
TEMP_OKBOOL
SPREAL°C
KPREAL%/K
TIREALs
DEV_KREALK
DEV_TMOTIME
BELT_SPDREALm/min
SPIRAL_LEN_MREALm
FAIL_PCTREAL%
ACKBOOL

Outputs

PortTypeUnit
REFRIG_PCTREAL%
RESIDENCETIME
RESIDENCE_VALIDBOOL
AT_TEMPBOOL
PROD_RELEASEBOOL
ALM_TEMP_DEVBOOL
ALM_TEMP_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
193
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499