CAPACITY_HEADROOM

Power and cooling utilisation against design capacity, with free kW on each and an explicit limiting-resource flag.

Validated application blockDCIM · MetricsIEC 61131-3v1.0.0

When to use it

Use CAPACITY_HEADROOM when a hall, a room or a whole site has a design electrical capacity and a design cooling capacity, and sales or capacity planning has to know how much more load can be placed and which of the two runs out first.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
KW_USEDREALkW
KW_DESIGNREALkW
COOL_USEDREALkW
COOL_DESIGNREALkW
DATA_OKBOOL—
WARN_PCTREAL%
CRIT_PCTREAL%
ALM_DBREAL%
ACKBOOL—

Outputs

PortTypeUnit
PWR_PCTREAL%
COOL_PCTREAL%
LIMITUSINT—
PWR_FREE_KWREALkW
COOL_FREE_KWREALkW
HEADROOM_KWREALkW
WORST_PCTREAL%
VALIDBOOL—
ALM_WARNBOOL—
ALM_CRITBOOL—
ALM_DATA_FAULTBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
10
Simulated scans
57
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download CAPACITY_HEADROOM — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.