BOILER_SEQ

Boiler plant staging against an outdoor-air hot-water reset, with anti-short-cycle protection in both directions.

Validated application blockBAS · Central PlantIEC 61131-3IEC 61499v1.0.0

When to use it

Use BOILER_SEQ when two or more boilers serve one hot-water plant and the supply setpoint should fall as the outdoor air warms, rather than making 82 °C water in April.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
HEAT_REQBOOL—
LOADREAL%
LOAD_OKBOOL—
HW_SUPREAL°C
HW_OKBOOL—
HW_SPREAL°C
OA_TEMPREAL°C
OA_OKBOOL—
N_BOILERSUSINT—
RESET_ENBOOL—
OA_LOWREAL°C
OA_HIGHREAL°C
SP_MAXREAL°C
SP_MINREAL°C
DB_KREALK
UP_PCTREAL%
DN_PCTREAL%
UP_DLYTIME—
DN_DLYTIME—
MIN_STAGE_TIMETIME—
FTM_TMOTIME—
ACKBOOL—

Outputs

PortTypeUnit
STAGEUSINT—
BOILERS_ONUSINT—
HW_RESET_SPREAL°C
VALIDBOOL—
ALM_FAIL_TO_MAINTAINBOOL—
ALM_SENSORBOOL—
ALM_CFG_ERRBOOL—

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
10
Simulated scans
878
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download BOILER_SEQ — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.